Eaton FH56 Overload Relay Heater
Regular price
$81.61
Couldn't load pickup availability
Heater Coil are Rated to Protect 40 Deg C Rise Motor, and Open and Dripproof Motor having a Service Factor of 1.15 Where the Motor and the Controller are at the Same Ambient Temperature; Ambient Temperature of Controller Lower than Motor by 26 Deg C Use One Size Smaller Coil; Ambient Temperature of Controller Higher than Motor by 26 Deg C Use One Size Larger Coil; Ultimate Tripping Current of Heater Coils is Approximately 1.25 Times the Minimum Current Rating
Specifications:
Trip Type: Thermal, Fast
Motor FLA: 38 to 41.5 Ampere
NEMA Size: 2 (Enclosed/Open)
Approval: UL, CSA
Used On: Type A and B Overload Relay