ABB GE Industrial Solutions SRPE30A30 Circuit Breaker Rating Plug
Couldn't load pickup availability
All Spectra, Power Break, and Power Break II circuit breakers use UL listed interchangeable rating plugs to establish or change the long time trip point of the circuit breaker. The key advantage of the rating plug is the flexibility of interchangeable rating plugs across the permissible current ratings of a given circuit breaker frame. Since the installed rating plug establishes the ampere rating of the breaker, the installer must verify the adequacy of the connected cable and/or bus bar ampacity. The National Electric Code allows cable size to be matched to the ampere rating established by the rating plug.
Specifications:
Type: Adjustable Instantaneous Trip, Electronic Trip
Frame Type: SE150
Maximum Breaker Current Rating: 30 Amp
Plug Current Rating: 30 Amp
Adjustable Instantaneous Trip Range: 87 to 415 Amp
Approval: UL, CSA, IEC
Accessory Type: Plugs