Burndy YA342N Compression Cable Lug
Couldn't load pickup availability
No Inspection Window is Ideal for More Corrosive Environments as the Barrel Transition is Not Open; Barrel is Designed with an Internal Chamfer at the Wire Entry to Ensure Smooth Insertion of the Wire, Preventing Possible Damaging of the Wire Strands; Long Barrel Allows for an Increased Number of Crimps Which will Increase the Mechanical Strength of the Connection; Two Hole Tongue/Tang is Recommended When Space Permits as the 2-Hole Feature Minimizes the Terminations from Loosening or Rotating Under Vibration, Movement, or Heat Cycling; Electro-Tin Plated Unless Otherwise Specified to Reduce Galvanic Corrosion (Bimetallic) and Resist Corrosive Elements; Connectors are Clearly Marked with Stamping and Barrel Color Coding; RoHS Compliant
Specifications:
Voltage Rating: 600 Volt to 35 Kilovolt
Conductor Material: Copper
Conductor Size: 500 KCMIL (Stranded)
Barrel Type: Long, Straight, Chamfered Entry
Barrel Length: 2.25 Inch
Pad Size: 1.55 Inch Width x 0.22 Inch Thickness
Number of Pad Holes: 2
Pad Hole Spacing: 1-3/4 Inch
Stud Size: 1/2 Inch
Color: Brown
Die Index: 20/299
Material: Electro Tin Plated Copper
Overall Length: 6.06 Inch
Approval: UL468A/B